Ireland adopts series compensation to unlock 400 kV capacity
Irish transmission corridors gain series compensation on the 400 kV system to boost transfer capacity across Oldstreet, Dunstown and Knockkyle substations.

Transmission system expansion frequently encounters severe barriers from land access, permitting timelines, and environmental planning. Rather than constructing additional overhead circuits, network operators are turning to active impedance management. In Ireland, series compensation equipment has been selected to raise transfer limits across the backbone 400 kV transmission network, focusing on key connection points at Oldstreet, Dunstown, and Knockkyle.
Inserting series capacitor banks directly into long transmission lines compensates for the inductive reactance of the conductors. By reducing electrical line length, this configuration allows higher power flows along existing rights-of-way while maintaining dynamic and transient stability. For asset engineers and system planners, this approach unlocks headroom for bulk power movement from peripheral generation zones toward demand centres without the protracted lead times associated with new line construction.
However, integrating series compensation fundamentally changes the operational environment for existing substation plant. Reducing series impedance increases prospective fault currents, directly altering short-circuit stress on circuit breakers, disconnectors, and power transformers. Furthermore, series capacitor installations introduce phenomena such as voltage inversion, current inversion, and subsynchronous resonance that can challenge legacy distance protection schemes. Protection relays, instrument transformers, and breaker arc-extinguishing chambers must withstand modified transient recovery voltages during line faults. Asset managers must therefore re-examine ratings and protection settings at adjacent substations before commissioning these installations.
What this means for asset owners in the UK and Ireland: Transmission and substation engineers in Ireland must prepare for complex staged outage windows during installation and testing at the affected 400 kV substations. Substation asset owners must review breaker ratings against elevated transient recovery voltages, re-evaluate secondary protection settings to prevent blind spots or spurious tripping caused by capacitor banks, and audit existing power transformer tap-changer controls for dynamic voltage swings across the reinforced corridor.